Description
Relevant Standard
EN 60598-1 | EN 61000-3-2 | IEC 60598-1 | IEC61000-3-2 |
EN 60598-2-22 | EN 61000-3-3 | IEC 60598-2-22 | IEC 61000-3-3 |
EN 61347-1 | EN 62471 | IEC 61347-1 | IEC 62471 |
EN 61347-2-13 | EN 62493 | IEC 61347-2-13 | IEC 62493 |
EN 61347-2-7 | EN 55015 | IEC 61347-2-7 | IEC 55015 |
EN 62778 | EN62031 | IEC 62778 | IEC62031 |
Product Parameter
Model No. : | LEK03-6NC | Battery: | Ni-Cd, 3.6V 2000mAh |
LED Chips: | Cree xt-e | Luminous Flux: | 150lm
|
Power Consumption: | 2x3W | Input Voltage: | AC220-240V~50/60Hz |
Charge time: | 24Hours | Emergency duration: | 3Hours |
ta: | 0~35ºC | Max. Case Temp.: | 70ºC |
Protection Class: | II | IP Rating: | IP20 |
Power factor: | 0.5 | Supply current: | 0.04A |
Operation: | Maintained or Non-maintained | Function: | MANUAL test |
Light distribution: | Path way (Standard) | ||
Door way (Optional) |
Maintained and Non-Maintained Function
∷ Maintained: Assemble wire connector
∷ Non-Maintained: Disassemble the wire connector
Photometrics
LEK03 Narrow Lens(Path Way) LEK03 Wide Lens(Door Way)
Dimension
Installation Diagram
Wire preparation:
0.5~1.5mm²
Special Note
∷ This product should be installed by a registered electrician in accordance with local standard and electrical regulations.
∷ Take care to ensure the mains supply is isolated before installation, Check the unit label for correct supply voltage and frequency.
∷ The whole luminaire should be replaced when they no longer meet their rated duration of operation after the corresponding recharge period.
∷∷ Normal Operation: The green indicator light on the bottom unit stays on. The LED will go out if the mains supply fails, if the internal charger is malfunctions, or if the unit is in test mode. The fixture must be charge 24 hours after installation.
∷∷ Battery: The battery is not replaceable; When battery no longer meet its rated duration of operation, after corresponding recharge period, the whole luminaire shall be replaced.
∷∷ LED: The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced;
∷∷ Test Switch: If pressed the test switch, LED indicator will go out and the fixture will operate from its battery supply.
∷∷ Auto Self Testing: Every 7 days for function tests and every 26 weeks for duration tests.